Connecting the power supply – Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual

Page 27

Advertising
background image

Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011

Installing the XM-440 Master Relay Module 27

Connecting the Power Supply

Power supplied to the module must be nominally 24 Vdc (±10%) and must be
a Class 2 rated circuit.

Wire the DC-input power supply to the terminal base unit as shown in Figure
2.8.

Figure 2.8 DC Input Power Supply Connections

42

Relay 2 N.C. 1

Relay #2 Normally Closed contact 1

43

Relay 3 N.C. 2

Relay #3 Normally Closed contact 2

44

No Connection

45

Relay 3 N.C. 1

Relay #3 Normally Closed contact 1

46

Relay 4 N.C. 2

Relay #4 Normally Closed contact 2

47

Relay 4 N.C. 1

Relay #4 Normally Closed contact 1

48

No Connection

49

Chassis

Connection to DIN rail ground spring or panel mounting hole

50

DNet V (-)

DeviceNet bus power input, negative side (black wire)

51

CAN_Low

DeviceNet bus connection, low differential (blue wire)

Terminal Block Assignments

No.

Name

Description

-

24V dc

Power

Supply

+

-

IMPORTANT

A Class 2 circuit can be provided by use of an NEC Class 2
rated power supply, or by using a SELV or PELV rated
power supply with a 5 Amp current limiting fuse installed
before the XM module(s).