Devicenet object (class id 03h), Class attributes, Instance attributes – Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual

Page 72: Class attributes instance attributes, Devicenet object (class id 03

Advertising
background image

Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011

72 DeviceNet Objects

DeviceNet Object
(Class ID 03

H

)

The DeviceNet Object is used to provide the configuration and status of a
physical attachment to DeviceNet.

Class Attributes

Instance Attributes

1

Setting the MAC ID causes the device to reset automatically, after which it will go online with the new MAC
ID.

2

The Baud Rate setting can not be set while Autobaud Disable is equal to 0. Applying the Baud Rate does not
occur until the Reset service to the Identity Object.

The MAC ID, Baud Rate,

and Autobaud Disable settings are stored in

non-volatile memory so they do not reset to the default with each power cycle.
The Baud Rate attribute supports the following settings:

• 0 = 125 kbps
• 1 = 250 kbps
• 2 = 500 kbps

The Baud Rate setting is used only when automatic baud rate detection is
disabled (Autobaud Disable = 1). When Autobaud Disable is set to zero (0),
the module ignores its Baud Rate setting and performs automatic baud rate

Table C.4 DeviceNet Object Class Attributes

Attr ID

Access
Rule

Name

Data Type

Default Value

1

Get

Revision

UINT

2

Table C.5 DeviceNet Object Instance Attributes

Attr ID

Access
Rule

Name

Data Type

Default Value

1

Get/Set

MAC ID

1

USINT

63

2

Get/Set

Baud Rate

2

USINT

0

3

Get

Bus-Off Interrupt

BOOL

0

4

Get/Set

Bus-Off Counter

USINT

0

5

Get

Allocation Information

STRUCT of
BYTE
USINT

0 255

100

Get/Set

Autobaud Disable

BOOL

0 (Ignore attribute 2 and always autobaud)