Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual

Page 54

Advertising
background image

Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011

54 Specifications

Relays

Number

Contacts

Failsafe

Latching

Time Delay

Voting Logic

Reset

Four relays, two sets of contacts each -
DPDT (2 Form C)
Four or eight additional relays when
connected to one or two XM-441 Expansion
Relay modules

250V AC, 50/60 Hz, 3 A Resistive

Normally energized (failsafe), or
Normally de-energized (non-fail-safe)

Latching, or
Non-latching

0 to 25.5 seconds, adjustable in 100msec
increments

Per relay, defined as “A out of B” where “B”
is up to 16 alarms and/or relays from any
XM measurement module(s) on the bus and
“A” is from 1 to “B”

Local reset switch on top of module
Remote reset switch wired to terminal base
Digital reset command via serial or
DeviceNet interface

Power

Module

Consumption

Heat Production

24V DC

200mA maximum

3.4 Watts (11.6 BTU/hr) maximum

Environmental

Operating Temperature

Storage Temperature

Relative Humidity

-20° to +65°C (-4 to +149°F)

-40 to +85°C (-40 to +185°F)

95% non-condensing

All printed circuit boards are conformally coated
in accordance with IPC-A-610C.

Physical

Dimensions

Terminal Screw Torque

Height: 3.8in (97mm)
Width: 3.7in (94mm)
Depth: 3.7in (94mm)

7 pound-inches (0.6Nm)

XM-440 Technical Specifications

Product Feature

Specification

Advertising