38 Installing the XM-440 Master Relay Module

Module Indicators

The XM-440 has six LED indicators, which include a module status (MS)
indicator, a network status (NS) indicator, and a status indicator for each Relay
(four in all). The LED indicators are located on top of the module.

Figure 2.16 LED Indicators

The following tables describe the states of the LED status indicators.

Module Status (MS) Indicator

1

Program Mode - Typically this occurs when the module configuration settings are being updated with the XM
Serial Configuration Utility. The module closes I/O connections with the XM measurement modules in its
scanlist. The alarm monitoring is stopped, the relay outputs are deactivated unless they are latched.
Configuration parameters can be read, updated and downloaded to the XM module.

2

Run Mode - The module establishes I/O connections with the XM measurement modules in its scanlist, collects
their alarm status, and controls its own relay outputs accordingly.

MASTER RELAY

1440-RMA00-04RC

Module Indicators

Color

State

Description

No color

Off

No power applied to the module.

Green

Flashing Red

Module performing power-up self test.

Flashing

Module operating in Program Mode

1

.

Solid

Module operating in Run Mode

2

.

Red

Flashing

• Application firmware is invalid or not loaded.

Download firmware to the module.

• Firmware download is currently in progress.
• Module is configured incorrectly. Verify that each

slave’s module type is correct.

Solid

An unrecoverable fault has occurred. The module may
need to be repaired or replaced.