Table 3

Pipe Diameter Table

Single Piping ONLY

40,000, 50,000, 60,000 & 75,000 Btuh Furnaces

40′ (12.2m) & (5) 90° elbows with 2″ (50.8mm) PVC pipe

80,000 & 100,000 Btuh Furnace

40′ (12.2m) & (5) 90° elbows with 3″ (76.2mm) PVC pipe

125,000 Btuh Furnace

40′ (12.2m) & (5) 90° elbows with 3″ (76.2mm) PVC pipe

The minimum vent length is 5’ (1.5m) of PVC. Elbows are

DWV Long Radius Type for 2” (50.8mm) and 3” (76.2mm)

vents.

If more than five elbows are required, reduce the length of both

the inlet and exhaust pipes 5(1.5m) for each additional elbow

used. If less than five elbow are required, the length can be

INCREASED by 5(1.5m) for each additional elbow NOT

used.
NOTE:
It is allowable to use larger diameter pipe and fitting than

shown in the tables but not smaller diameters than shown.

Table 4

Pipe Diameter Table

Dual Piping ONLY

40,000, 50,000, 60,000 & 75,000 Btuh Furnaces

40′ (12.2m) & (5) 90° elbows with 2″ (50.8mm) PVC pipe

80,000 & 100,000 Btuh Furnace

40′ (12.2m) & (5) 90° elbows with 3″ (76.2mm) PVC pipe

125,000 Btuh Furnace

40′ (12.2m) & (5) 90° elbows with 3″ (76.2mm) PVC pipe

The minimum vent length is 5’ (1.5m) of PVC. Elbows are

DWV Long Radius Type for 2” (50.8mm) and 3” (76.2mm)

vents.

If more than five elbows are required, reduce the length of both

the inlet and exhaust pipes 5(1.5m) for each additional elbow

used. If less than five elbow are required, the length can be

INCREASED by 5(1.5m) for each additional elbow NOT

used.
*
Feet (M) of pipe is whichever pipe run is the longest, either

inlet or outlet side.

For venting table, see“Concentric Termination Kit” in

this manual.

Vent Termination Clearances

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury

or death.
Inlet and outlet pipes may NOT be vented directly above each

other.

!

WARNING

1. Determine termination locations based on clearances

specified in following steps and as shown in Fig. 8, 9, and
22 through 30.

For “Concentric Termination Kit” clearances, see Fig. 32, 33, 34,

35 and 36 in this manual.

2. This furnace is Dual Certified and can be installed as a single

pipe appliance (all combustion from inside the structure) or
as a direct vent appliance where all combustion air is taken
from outside the structure.

3. For Direct Vent installation, refer to Fig. 8 for vent

termination.

4. For Single Pipe installation refer to Fig. 9 for vent

termination clearances.