58h d v – Carrier DIRECT VENT 4 58HDV User Manual

Page 30

Advertising
background image

30

Combustion
Air

Exhaust

12

″″ (304.8mm)

Min. Grade or
Snow Level

36” Min

2” (50.8mm) Max

36”Min

OR

(914.4mm)

(914.4mm)

A07718

Fig. 26 -- Concentric Vent and Combustion--Air

Roof Termination

“A”

Vent

Dimension “A” is touching or 2

″ (50.8mm) maximum separation.

25--22--02d

Vent

Combustion Air

1

(25.4mm)

Maximum

Exhaust

A07695

Fig. 27 -- Concentric Vent and Combustion Air

Sidewall Termination

12

″″ (304.8mm) Min.

Grade or Snow Level

8

(457.2mm) Min.

20

(6.1m) Max.

“A”

“A”

Exhaust

Inlet

Dimension “A” is touching or 2

″ (50.8mm) maximum separation.

18

(457.2mm) Min. for Cold Climates

[Sustained 0

°F(-17°C) and below for

24 hours or more consecutive hours]

8

Min.

A07696

Fig. 28 -- Sidewall Inlet Vent and Exhaust--Air Termination

Exhaust

8

(203.2mm) Min.

Inlet

“A”

“A”

Dimension “A” is touching or 2

″ (50.8mm) maximum separation.

12

(457.2mm)

Min. Grade or
Snow Level

18

(457.2mm) Min. for Cold Climates

[Sustained 0

°F(-17°C) and below for

24 hours or more consecutive hours]

8

(203.2mm) Min.

20

(6.1m) Max.

A07697

Fig. 29 -- Sidewall Inlet Vent and Exhaust--Air Termination

with Exterior Risers

12

″″ (304.8mm)

Min. Grade or
Snow Level

Exhaust

8

(203.2mm) Min.

20

(6.1m) Max.

25--22--43

Inlet

18

(457.2mm) Min. for Cold Climates

[Sustained 0

°F(-17°C) and below for

24 hours or more consecutive hours]

A07698

Fig. 30 -- Rooftop Inlet Vent and Exhaust--Air Termination

58H

D

V