Downflow right--side vent and trap, See fig. 15), 58h d v – Carrier DIRECT VENT 4 58HDV User Manual

Page 22

Advertising
background image

22

AIR

F

L

O

W

OFF

ON

Drain Connector Black
PVC

3

/

4

CPVC (Loose parts bag)

Trap Connection

“Clamp ears”
Pointed OUT

Preassemble &
insert into furnace

Single Pressure Switch Detail

Dual Pressure Switch

Tee Trap White PVC
(loose parts bag)

Drain Tube Corrugated
Black,

5

/

8

(16 mm)

WARNING
Move Caps to
top of trap

Drain Tube Black Rubber,

5

/

8

ID (16 mm) Cut to fit & Clamps

(loose parts bag)

AIR

FL
O

W

Barbed Coupling

1

/

2

(13 mm) OD

(Loose Parts Bag)

Drain Hose
Black Rubber

1

/

2

(13 mm) ID Cut to

Fit & Clamps

Either: The PVC
Drain Tee or a field
supplied 2

(51 mm) PVC Tee

Rotate downward
5

° to 10°

NOTE: Built--in channel will
be angled 5

° to 10° also.

SIDE VIEW

Plastic Cap
Yellow or black

Vent Drain
& Clamps

INLET

On Some
Models
ONLY

2

(51 mm) PVC Coupling

Coupling & Clamps
(Optional)

Relief Tube
Black Rubber

3

/

16

(5 mm) ID

Elbow Tube Black Rubber

1

/

2

(13 mm) ID & Clamps

(Loose Parts Bag)

ID & Clamps

PVC X

1

/

2

(13 mm)

(19 mm)

A07768

Fig. 15 -- Downflow Right--Side Vent and Trap

Downflow Right--Side Vent and Trap

(See Fig. 15)

Remove the drain tee if installed.
Disconnect the hoses from the trap assembly, and remove trap and

trap mounting bracket from the blower compartment. Using cover
plate and gasket provided in the loose parts bag, cover the hole

from the burner compartment to the blower compartment and

secure with screws.
Move the caps to the top of the trap and mount the trap externally

to the right side of the unit using the two(2) screws provided.
Connect the corrugated drain tube from the transition box to the

trap as shown. If an extension is required, use the black PVC tube

connector and the black

5

/

8

″ (15.9mm) ID drain tube in the loose

parts bag. Cut tube to length. Secure all connections with clamps.
Connect the drain hose from the Vent Drain to the trap. If an
extension is required, use the black

1

/

2

″ (12.7mm) OD barbed

coupling, connect a black

1

/

2

″ (12.7mm) ID elbow tube and a

suitable section of a

1

/

2

″ (12.7mm) ID drain tube to make

connection from the vent drain to the trap. Secure all connections

with clamps.

Install the vent pipe grommet into the casing
Cut an appropriate length of 2″ (50.8mm) PVC pipe long , enough

to exit the cabinet and connect the vent drain to either:

S

A 2″ (50.8mm) PVC coupling fastened onto the drain tee

Install tee trap into bottom section of tee and glue pipe.
Remove knockout from the side of the furnace casing where drain

tube will exit.
Connect the tee trap and the main drain line exiting the casing as

shown in Fig. 15.
NOTE: Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both
the external trap and the external tee trap must be primed
before operation.
Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may
be installed as shown for future servicing of the vent system.

58H

D

V