Table 7

NATURAL GAS MANIFOLD PRESSURE (in wc)

20,000 BTU per burner

MEAN ELEVATION ABOVE SEA LEVEL ft(m)

HEATING

VALUE at

ALTITUDE

BTU/CU.

FT.

0 to 2000

(0 to 609.6)

2001 to 3000

{

(609.9 to 914.4)

{

3001 to 4000

(914.7 to 1219.2)

4001 to 5000

(1219.5 to 1524)

5001 to 6000

(1524.3 to 1828.8)

6001 to 7000

(1829.1 to 2133.6)

7001 to 8000

(2133.9 to 2438.4)

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

HI

LO

HI

LO

HI

LO

HI

LO

HI

LO

HI

LO

HI

LO

700

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

44

3.7

1.8

725

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

44

3.7

1.8

44

3.4

1.7

750

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

44

3.5

1.7

44

3.2

1.6

775

----

----

----

----

----

----

----

----

----

----

----

----

44

3.5

1.7

44

3.2

1.6

46

3.8

1.9

800

----

----

----

----

----

----

----

----

----

44

3.6

1.8

44

3.3

1.6

45

3.7

1.8

46

3.6

1.7

825

----

----

----

----

----

----

44

3.7

1.8

44

3.4

1.7

45

3.8

1.8

46

3.6

1.8

47

3.8

1.9

850

----

----

----

----

----

----

44

3.5

1.7

44

3.2

1.6

46

3.7

1.8

46

3.4

1.7

47

3.6

1.7

875

----

----

----

44

3.5

1.7

44

3.3

1.6

46

3.8

1.9

46

3.5

1.7

47

3.7

1.8

48

3.8

1.9

900

----

----

----

44

3.3

1.6

45

3.7

1.8

46

3.6

1.8

47

3.8

1.8

47

3.5

1.7

48

3.6

1.8

925

44

3.7

1.8

44

3.2

1.5

46

3.7

1.8

46

3.4

1.7

47

3.6

1.8

48

3.7

1.8

48

3.4

1.7

950

44

3.5

1.7

45

3.6

1.8

46

3.5

1.7

47

3.7

1.8

47

3.4

1.7

48

3.5

1.7

49

3.8

1.9

975

44

3.3

1.6

46

3.6

1.8

47

3.8

1.9

47

3.5

1.7

48

3.7

1.8

48

3.4

1.6

49

3.6

1.8

1000

44

3.2

1.6

46

3.4

1.7

47

3.6

1.8

48

3.8

1.8

48

3.5

1.7

49

3.8

1.8

49

3.4

1.7

1050

46

3.6

1.8

47

3.5

1.7

48

3.7

1.8

48

3.4

1.7

49

3.7

1.8

----

----

----

----

----

----

1100

47

3.8

1.8

48

3.7

1.8

48

3.4

1.7

49

3.7

1.8

----

----

----

----

----

----

----

----

----

Conversion: 1 in wc = 249 Pa

Bold-- indicates factory orifice size.

NOTE: Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI
Z223.1--2006/NFPA 54--2006 or National Standard of Canada, Natural Gas and Propane Installation Code CSA B149.1--05.
In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design--certified by CSA.
{

In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to 1371.6m)

above sea level. Use the 2001 to 3000 (609.9 to 914.4m) column in Table 7 and Table 8.

Table 8

PROPANE GAS MANIFOLD PRESSURE (in wc)

20,000 BTU per burner

MEAN ELEVATION FEET ABOVE SEA LEVEL ft(m)

HEATING VALUE

at ALTITUDE

BTU/CU. FT.

0 to 2000

(0 to 609.6)

2001 to 3000

{

(609.9 to

914.4)

{

3001 to 3999

(914.7 to

1219.2)

4001 to 5000

(1219.5 to 1524)

5001 to 6000

(1524.3 to

1828.8)

6001 to 7000

(1829.1 to

2133.6)

7001 to 8000

(2133.9 to

2438.4)

Hi

Lo

Hi

Lo

Hi

Lo

Hi

Lo

Hi

Lo

Hi

Lo

Hi

Lo

2500

10.0

4.9

8.9

4.4

8.4

4.1

10.0

4.9

10.0

4.9

10.0

4.9

10.0

4.9

Orifice Size

#55

#55

#55

#56

#56

#56

#56

Conversion: 1 in wc = 249 Pa
NOTE: Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code A

NSI

Z223.1--2006/NFPA 54--2006 or National Standard of Canada, Natural Gas and Propane Installation Code CSA B149.1--05.

In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design--certified by CSA.
{

In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to 1371.6m)

above sea level. Use the 2001 to 3000 (609.9 to 914.4m) column in Table 7 and Table 8.
The burner orifice part numbers are as follows:

Orifice

Part #

Orifice

Part #

41

333730--701

42

333730--702

43

333730--703

44

333730--704

45

333730--705

46

333730--709

47

333730--710

48

333730--711

49

333730--712

54

333730--706

55

333730--707

56

333730--708

Changing Orifices for High Altitude

ELECTRICAL

SHOCK, FIRE

OR

EXPLOSION

HAZARD
Failure to follow this warning could result in personal injury,

death, and/or property damage.
Turn OFF electric power (at disconnect) and gas supply (at

manual valve in gas line) when installing orifices. Installation

of orifices requires a qualified service technician.

!

WARNING

NOTE: Main burner orifices can be changed for high altitudes.

1. Disconnect gas line from gas valve.
2. Remove manifold from furnace.
3. Remove the orifices from the manifold and replace them

with properly sized orifices.

4. Tighten orifices so it is seated and gas tight. (See Fig. 39.)