Confined space installation, Requirements – Carrier DIRECT VENT 4 58HDV User Manual

Page 9

Advertising
background image

9

Confined Space Installation

NOTE: A confined space is defined as an area with less than 50
cubic feet (1.4

3

M)per 1,000 BTUH (2.33 cm

2

/kW) input rating for

all gas appliances installed in the area.

Requirements

1. Provide the space with sufficient air for proper combustion

and ventilation of flue gases using horizontal or vertical

ducts or openings.

2. Fig. 6 illustrates how to provide combustion and ventilation

air. A minimum of two permanent openings, one inlet and

one outlet, are required.

a. One opening MUST commence within 12″ (304.8mm)

of the floor and the second opening MUST commence

within 12″ (304.8mm) of the ceiling.

b. Size openings and ducts per Table 1.

c. Horizontal duct openings require 1 square inch of free

area per 2,000 BTUH (11 cm

2

/kW) of combined input

for all gas appliances in the space (see Table 1).

d. Vertical duct openings or openings directly

communicating with the outdoors require 1 square inch
of free area per 4,000 BTUH (5.5 cm

2

/kW) for

combined input of all gas appliances in the space (see

Table 1).

Minimum One Inlet and One Outlet Air Supply is Required
May be in any Combination Shown

Inlet Air Opening Must be Within12

of floor

Outlet Air Opening Must be Within12

of ceiling

(1) 1 Square Inch per 4000 BTUH

(2) 1 Square Inch per 2000 BTUH

This installation NOT approved in Canada

Gas Vent

Gable Vent

Ventilated Attic

Top Above Insulation

Alternate Inlet Air (1)

Ventilated Crawl Space

Outlet Air (1)

Soffit Vent

Outlet
Air (1)

Inlet
Air (1)

Outlet
Air (2)

Inlet
Air (2)

Gas Vent

Inlet
Air (2)

Soffit Vent

Gas Vent

Gable Vent

Ventilated Attic

Top Above Insulation

Inlet
Air (1)

OutletAir (1)

alternate Inlet Air (1)

A07704

Fig. 6 -- Outside Air

(This is ONLY a guide. Subject to codes of country having jurisdiction).

3. One opening MUST be within 12″ (304.8mm) of the floor

and the second opening within 12″ (304.8mm) of the

ceiling.

a. 1 sq. in of free area per 3,000 BTUH (7 cm

2

/kW) for

combined input of all gas appliances in the space (see

Table 1) and

b. not less than the sum of the areas of all vent connectors

in the space.

The opening shall commence within 12″ (304.8mm) of the top of

the enclosure. Appliances shall have clearances of at least 1″

(25.4mm) from the sides and back and 6″ (152.4mm) from the

front. The opening shall directly communicate with the outdoors or
shall communicate through a vertical or horizontal duct to the

outdoors or spaces (crawl or attic) that freely communicate with the

outdoors.

4. Size openings and ducts per Table 1.

a. Indoor openings that comply with the Indoor

Combustion Air Method below and

b. Outdoor openings located as required in the Outdoor

Combustion Air Method above and

c. Outdoor openings sized as follows.

(1.) Calculate the Ratio of all Indoor Space volume

divided by required volume for Indoor

Combustion Air Method.

(2.) Outdoor opening size reduction Factor is 1 minus

the Ratio in 1) above.

(3.) Minimum size of Outdoor openings shall be the

size required in Outdoor Combustion Air Method

above multiplied by reduction Factor.

5. Horizontal duct openings require 1 square inch of free area

per 2,000 BTUH of combined input for all gas appliances in
area (see Table 1).

6. Vertical duct openings or openings directly to outside

require 1 square inch of free area per 4,000 BTUH (5.5
cm

2

/kW) for combined input of all gas appliances in area

(see Table 1).

58H

D

V

Advertising