Warning, Caution, Installation positions – Carrier DIRECT VENT 4 58HDV User Manual

Page 5: Location and clearances, Installation requirements, Installation

Advertising
background image

5

INSTALLATION

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury

or death.
This furnace can NOT be common vented or connected to any

type B, BW or L vent or vent connector, nor to any portion of

a factory--built or masonry chimney. If this furnace is replacing

a previously common-vented furnace, it may be necessary to

resize the existing vent and chimney to prevent oversizing

problems

for

the

other

remaining appliance(s). See Venting and Combustion Air

Check in Gas Vent Installation section. This furnace MUST be

vented to the outside.

!

WARNING

Installation Positions

This furnace can be installed in an upflow, horizontal (either left or

right) or downflow airflow position. DO NOT install this furnace
on its back. For the upflow position, the return air ductwork can be

attached to either the left or right side panel and/or the bottom. For
horizontal and downflow positions, the return air ductwork must be

attached to the bottom. The return air ductwork must never be
attached to the back of the furnace.

Location and Clearances

1. Refer to Fig. 1 for typical installation and basic connecting

parts required. Refer to Fig. 4 for typical horizontal direct
vent installation and basic connecting parts required. Supply

and return air plenums and duct are also required.

2. If furnace is a replacement, it is usually best to install the fur-

nace where the old one was. Choose the location or evaluate

the existing location based upon the minimum clearance and
furnace dimensions (Fig. 2).

FROZEN AND BURST PIPE HAZARD
Failure to follow this caution may result in property damage.
Special precautions MUST be made is installing furnace in an

area which may drop below freezing. This can cause improper

operation or damage to equipment. If furnace environment

has the potential of freezing, the drain trap and drain line must

be protected. The use of electric heat tape or RV antifreeze is

recommended for these installations. (See “Condensate Trap

Freeze Protection Section”)

CAUTION

!

Vent Pipes MUST be
supported
Horizontally and

Vertically

*8

″ (203.2mm) Min.

20

′ (6.1m) Max.

in same atmospheric zone

*8

″ (203.2mm) Min.

20

′ (6.1m) Max.

in same
atmospheric
zone

Coupling on ends of
exhaust pipe. Total
pipe & coupling out-
side structure = 8

(203.2mm)

Aluminum or non--rusting shield recommended.
(See Vent Termination Shielding for dimensions).

* Increase minimum from 8

″″ (203.2mm) to 18(457.2mm) for cold climates (sus-

tained temperatures 0

° F (-17° C) and below for 24 or more consecutive hours).

DI

SCHARG

E

A

IR

25--23--33

Inlet Pipe
(not used on
Single Pipe
model)

A07700

Fig. 1 -- Typical Upflow Installation

*8

″ Min. (203 mm)

20

′ Max. in same (6 M)

atmospheric zone

Vent Pipes MUST
be supported Horizon-
tally and Vertically

*

Increase minimum from 8

″″ to 18(203 to 457 mm) for cold climates (sustained temperatures

0

°F ( - 1 8 °C ) and ) below for 24 or more consecutive hours).

See Vent Termination
Shielding in Vent Section.

*8

″ Min. (203 mm)

20

′ Max. (6.1 M)

in same
atmospheric zone

8

″ Min. (203 mm)

Coupling on inside
and outside of wall to
restrain vent pipe

25--23--33a

Inlet Pipe
(not used on
Single Pipe
model)

A07762

Fig. 2 -- Typical Downflow Installation

Installation Requirements

1. Install furnace level.
2. This furnace is NOT to be used for temporary heat of

buildings or structures under construction.

3. Install furnace as centralized as practical with respect to the

heat distribution system.

4. Install the vent pipes as short as practical, and in accordance

to these instructions. (See Vent and Combustion Air Piping

section).

5. Maintain clearance for fire safety and servicing. A front

clearance of 24″ (609.6mm) required and 30″ (762mm)

recommended for access to the burner, controls and filter.
See clearance requirements in Fig. 4.

6. Use a raised base for upflow furnace if the floor is damp or

wet at times.

7. For downflow installations, non combustible subbase must

be used under the furnace unless installation is on a non
combustible floor surface. This requirement applies even

when a coil box or cabinet is used.

58H

D

V

Advertising