Installation and Operation Manual - Supervisor Mode Parameters

47

4.56 Interfacing a PLC to the Belt Scale

System

Within the

BCi

, there are setpoints which contain four

numeric variables:

Value (target)

Bandwidth

Preact

Hysteresis

These setpoints can be read or written from a PLC.
The command to a write the value is a 304 and to read
the value is a 320. The other write values are 305, 306,
and 307 for the hysteresis, bandwidth and preact. The
read values are 321, 322, and 323. You will only be
using the value variables in each setpoint.

The following setpoints will contain these values from
the variable needed in the belt scale:

Table 4-2. Setpoint Values

Setpoint

Value

Description

SP4

Clear totalizer when set to any non-zero
value.

SP97

Return belt speed

SP98

Return TN/HR (rate)

SP99

Return load

SP100

Return totalizer value

4.57 Special Serial Commands

In addition to the integrator’s standard EDP command
set (see your 920i installation manual, PN 69887), it
have seven special commands specific to the belt scale
functions. those commands are shown in Table

Command

Function

F#1=MT

Master total

F#1=BT

Batch total

F#1=MR

Master reset

F#1=BR

Batch total reset

F#1=TPH

Tons per hour

F#1=UID

Integrator ID

F#1=RT

Set totalizer

Table 4-3. Key Press Serial Commands