1 important notes, 1 two power sources, 2 i/o power and manual panel same phase power – Rice Lake CB-2 Concrete Batch Controller Version 1.0 User Manual

Page 9: 3 unused inputs must be jumpered to 120v, Two power sources, I/o power and manual panel same phase power, Unused inputs must be jumpered to 120v

Advertising
background image

Installation

5

2.1

Important Notes

2.1.1

Two Power Sources

The CB-2 requires two separate power sources to run. The power cord that came wired to your CB-2 ONLY

powers the electronics. This power should come from a quality UPS with power conditioning. This clean power

must be separated as far as possible (distance in the electrical circuit) from the power source used to power the

motion control on the batch plant.
Another power source must be brought into the CB-2 to power the I/O (output relays), that control the plant. No

power cord is supplied because this power must be brought directly from its own circuit or fed from another

manual panel.

2.1.2

I/O Power and Manual Panel Same Phase Power

The CB-2 and manual panel will both be wired to the same I/O points for most plant controls (exceptions are air

compressors or other equipment the CB-2 doesn’t control in automatic mode). Because of this, it is critical that

the 120V “hot” that is used for the CB-2 I/O power, is the same “hot” phase used by the manual panel.

2.1.3

Unused Inputs Must be Jumpered to 120V

The CB-2 uses 120V input signals from various sensors for positive and negative feedback. At a minimum, the

CB-2 requires the following signals:

Cement discharge gate closed (Terminal 4-13 - Rack 2, Point 7)

Aggregate discharge gate closed (Terminal 4-15 - Rack 2, Point 8)

Aggregate conveyor running (Terminal 4-9 - Rack 2, Point 5)

E-Stop not pressed. This is fed 120VAC from inside the CB-2 automatic panel if 120V I/O power is

supplied

If your plant is not equipped with any of these sensors, you must get 120VAC to these inputs to satisfy the CB-2

interlocks. The best place to get 120VAC is to jumper from terminals 6, 7, 8 on the top row of the main junction

block.

Advertising