0 edp commands, 1 the edp command set, 1 key press commands – Rice Lake IQ Plus 355 Installation Manual V1.17 User Manual

Page 33: Edp commands, Key press commands, Section 6.0 or v, Section 6.0 for mor

Advertising
background image

EDP Commands

29

6.0

EDP Commands

The IQ plus 355 indicator can be controlled by a

personal computer or remote keyboard connected to

the indicator EDP port. Control is provided by a set of

EDP commands that can simulate front panel key

press functions, display and change setup parameters,

and perform reporting functions. The EDP port

provides the capability to print configuration data or

to save that data to an attached personal computer.

This section describes the EDP command set and

procedures for saving and transferring data using the

EDP port.

6.1

The EDP Command Set

The EDP command set can be divided into five

groups: key press commands, reporting commands,

the RESETCONFIGURATION special function

command, parameter setting commands, and transmit

weight data commands.
When the indicator processes an EDP command, it

responds with the message

OK

. The

OK

response

verifies that the command was received and has been

executed. If the command is unrecognized or cannot

be executed, the indicator responds with

??

.

The following sections list the commands and

command syntax used for each of these groups.

6.1.1

Key Press Commands

Key press EDP commands (see Table 6-1) simulate

pressing the keys on the front panel of the indicator.

Most commands can be used in both setup and

weighing mode. Several of the commands serve as

“pseudo” keys, providing functions that are not

represented by a key on the front panel.
For example, to enter a 15-pound tare weight using

EDP commands:

1. Type K1 and press

ENTER

(or

RETURN

).

2. Type K5 and press

ENTER

.

3. Type KTARE and press

ENTER

. The display

shifts to net mode when the tare is entered.

Command

Function

KZERO

In weighing mode, press the ZERO key

KGROSSNET

In weighing mode, press the GROSS/
NET key

KGROSS

Go to gross mode (pseudo key)

KNET

Go to net mode (pseudo key)

KTARE

Press the TARE key

KUNITS

In weighing mode, press the UNITS key

KPRIM

Go to primary units (pseudo key)

KSEC

Go to secondary units (pseudo key)

KNEWID

Enter new ID (pseudo key)

KPRINT

In weighing mode, press the PRINT key

KLEFTARROW

In setup mode, move left in the menu

KRIGHTARROW

In setup mode, move right in the menu

KUPARROW

In setup mode, move up in the menu

KDOWNARROW

In setup mode, move down in the menu

K0

Press number 0 (zero)

K1

Press number 1

K2

Press number 2

K3

Press number 3

K4

Press number 4

K5

Press number 5

K6

Press number 6

K7

Press number 7

K8

Press number 8

K9

Press number 9

KDOT

Press the decimal point (.)

KENTER

Press the ENTER key

Table 6-1. EDP Key Press Commands