0 appendix, 1 error messages, 1 displayed error messages – Rice Lake IQ Plus 355 Installation Manual V1.17 User Manual

Page 39: Appendix, Displayed error messages

Advertising
background image

Appendix

35

7.0

Appendix

7.1

Error Messages

The IQ plus 355 indicator provides a number of error messages. When an error occurs, the message is shown on

the indicator LED display. Error conditions can also be checked remotely by using the XE EDP command as

described in Section 7.1.2.

7.1.1

Displayed Error Messages

The IQ plus 355 provides a number of front panel error messages to assist in problem diagnosis. Table 7-1 lists

these messages and their meanings.

Error Message

Description

Solution

E A/D

A/D physical error

Call Rice Lake Weighing Systems (RLWS) Service.

EEEROM

EEPROM physical error

EVIREE

Virgin EEPROM

Use TEST menu to perform DEFLT (restore defaults) procedure, then
recalibrate load cells.

EPCKSM

Parameter checksum error

EACKSM

A/D calibration checksum error

A/D converter requires recalibration. Call RLWS Service.

EFCKSM

Printer format checksum error

Call RLWS Service.

ELCKSM

Load cell calibration checksum error

Recalibrate load cells.

EIDATA

Internal RAM checksum error

Call RLWS Service.

E REF

A/D reference error

A/D converter requires recalibration. Call RLWS Service.

Error

Internal program error

Check configuration. Run XE command (see Section 7.1.2 on
page 36
) to determine error type.

Call RLWS Service if unable to clear error by cycling power or if error
recurs.

OVERFL

Overflow error

Weight value too large to be displayed.

- - - - - -

Gross > overload limit

Gross value exceeds overload limit. Check configuration or signal
input level. Overload can be caused by input signal > 45mV or
common mode voltage > 950 mV.

_ _ _ _ _ _

A/D underrange

A/D reading < –4 mV. Check scale for binding or damage.

Table 7-1. IQ plus 355 Error Messages

Advertising