Chapter 4

Chapter 4 Configuration

● ● ● ● ●

Chapter 4 covers the settings used to prepare the controller for calibration and operation.
The Setup procedures require Allen-Bradley’s RSLogix™ 5000, Allen-Bradley RSLinx®
or RSLinx® Lite for use in the CompactLogix™ system, or RSLogix 500 for the
MicroLogix™ 1500 system.

Power Check

To make or change settings,
there must be power to both the
PLC and the module. Verify that
the LED’s are lit for normal
operation.

Module LED’s

LEDS

Scale Data LED’s

Flashing Green

Feeder is on

Steady Green Running

(Normal)

Steady Red

Error Read Failure or Error eeprom write. Contact HI
Customer Support

Flashing Red

Read Convert Error.

LED is Off

Channel is Inactive

OK Module Status LED

Brief Steady

During power up the LED lights Red for about one second.

Flashing Green

In Program mode. (Normal)

Steady Green

In Run Mode. (Normal)

Steady Red

Config. Fault The eeprom checksum failed - bad serial
eeprom

(Backplane Available)

Data or blank serial eeprom. Contact HI Customer Support.

Steady Red

Internal Hardware watchdog timer fault (e.g. bad Hardware
or Firmware). ASIC is non-operational.

Flashing Red

Communication Error.