Hardy HI 1769-FC User Manual
Page 24
19
●
●
●
●
●
Chapter 4
I/O Configuration Dialog Box
Step 3: From the I/O Configuration dialog box, under the “#” column heading, click on
#1 or the next open slot number available.
Step 4: In the “Current Cards Available” double click on “Other – Requires I/O Type
Card ID” under the Description column heading.
Step 5: Enter the following in the appropriate text fields:
On some PLC platforms it may be necessary to enter the Vendor ID, the Product
Type, the Product Code, Input/Output Words and Extra Data Length. See
Below:
HARDY_VENDOR_ID 0x102 (258 decimal)
HARDY_PRODUCT_TYPE 0x65 (101 decimal)
HARDY_PRODUCT-CODE 5
Input Words – 32
Output Words – 32
Extra Data Length –192
Step 6: Click on the “Apply” button
Step 7: “OTHER” appears under the Part# column heading
I/O Configuration Dialog Box
Step 8: The HI 1769-FC is configured and ready to communicate with the MicroLogix
1500 Processor.
Configuring the HI 1769-FC Feeder Control Module in the RSLogix
5000 for CompactLogix with the HI 1769-FC Feeder Control Module
To set up communication between the CompactLogix Processor and the Feeder Control
Module as a generic module you will need to do the following in RSLogix 5000:
Step 1: Under project, click on the + next to I/O Configuration