Setting up communications – Hardy HI 1769-FC User Manual

Page 22

Advertising
background image


17

Chapter 4

Setting Up Communications

Linking the MicroLogix 1500 processor with the HI 1769-FC Feeder
Control Module

To set up communication between the MicroLogix 1500 Processor and the Feeder
Control Module you will need to do the following in RSLogix 500

Step1: We assume you have a project open or have created a new project. For

instructions please see your RS LOGIX 500 manual. The setup instructions
begin from this point. Under project, click on the + next to the controller. Click
on “I/O Configuration”. The I/O Configuration dialog box appears.


Step 2: From the I/O Configuration dialog box, under “#” column heading click on #1

or the next open slot number available.

I/O Configuration Dialog Box

Step 3: Click on the “Read IO Config” button. The “Read IO Configuration from Online

Processor” dialog box appears.

Read IO Configuration from Online Processor Dialog Box