Output table overview, First word - 0: command number – Hardy HI 1769-FC User Manual

Page 34

Advertising
background image


29

Chapter 4

Output Table Overview

To configure the module, you send commands via the PLC output table.

The 1769 module uses 32 16-bit INT words in and out. Only 5 words of the output table
are normally used. (Command 0X5E uses ten and 0X5F uses seven and 0x62 uses 9.)

Parameters can be read (READPARAM) or written (WRITEPARAM) one at a time:

 To read a parameter, put the readparam command number in word 0, the format

word in word 1, and the parameter’s ID number in word 4 of the output table.

 To write a parameter, put the writeparam command number in word 0, the

format word in word 1, and the parameter’s value in words 2 and 3, and the
parameter ‘s number in word 4 of the output table.

First Word - 0: Command Number

The first word in the output table is a command. The possible commands are:

Command

Hex

Description

NOCMD

0x0

No command

STARTCMD

0x1

START

STOPCMD

0x2

STOP - once to pause; twice to Idle.

REFILLCMD

0x3

REFILL

WRITENONVOL
ATILE

0x4

Saves all parameters (including calibration constants) to
the non-volatile memory. Error Return Values: None

MANUALCMD

0x5

Enters manual mode

ABORTCMD

0x6

Stop, go straight to IDLE mode

CLEARALARMS

0x7

Clear all alarms from the rate status word.

RELOADNONVOL
ATILE

0x10

Causes the module to re-read the values stored in its non-
volatile memory. Parameters changed since the last write
non-volatile command are overwritten. Can be used to
abort a calibration or parameter entry session. No error
return values.

RATE_CAL_5_P
OINTS_DEFINED

0x5E

Runs the 5-point rate calibration at percentage outputs
defined at words 5-9. The percentages have 0 decimal
places. They must be > 0, < 100, and in ascending order,
with a minimum of 10 between them.

RATE_CAL_2_P
OINTS_DEFINED

0x5F

Runs the 2-point rate calibration at percentage outputs
defined at words 5-6. The percentages have 0 decimal
places, and must be > 0, < 100, and in ascending order,
with a minimum of 10 between them. This calibration
operates at points 2 and 4 of a 5-point rate calibration. The
other points are filled with data based on these 2 points.

Word

Command structure write

0 Command

number

1

Format word (see Format Word below)

2 Value

(LSW)

3

Value (MSW)

4 Parameter

ID