Chapter 4

Refill OP Adjust %/wgt

This is the OP (Output Percentage) Adjust % per unit of wgt. The OP Adjust %/wgt
factor may be estimated by the formula [OPHigh - OPLow]/[HiWeight-LoWeight],
where OPHigh is the observed output percent at gross weight HiWeight, and OPLow is
the output percent when gross weight = LoWeight.

The weight of an ingredient in a hopper can affect the rate of feed. For example, a liquid
at the base of a full hopper is under greater pressure than a liquid at the base of a near
empty hopper. If no adjustment is made, the liquid flows out faster when the hopper is
full than when it is low. When the OP Adjust parameter is ON (i.e., not set to OFF), the
OP Adjust %/wgt value will adjust the OP% rate to compensate for any change in weight
of the ingredient in the hopper. OP Adjust On Learn is used to calculate this value.

Range: -100 to +100 up to six decimal places (Default 0.0)

Parameter 19

Wait Time

Time the controller waits for the material to settle before it calculates the batch total.
Seconds, 0 decimal places. Must be > or = 0

Parameter 20

Low Alarm Shut Down Rate

If the actual flow rate is below the setpoint, the Lo Shutoff alarm can be configured to
signal an alarm condition that can either shut the process down or lower the output to a
set percentage (See Shutoff % Out below). The decimal point is positioned based on the
Rate DP parameter.

NOTE

The Lo Shutoff alarm value must be equal to or less than the lowest set point value.

Range: No limits

Parameter 21

High Alarm Shut Down Rate

If the actual flow rate is above the setpoint, the Hi Shutoff alarm can be configured to
signal an alarm condition that can either shut the process down or lower the output to a
set percentage (See Shutoff % Out below). The decimal point is positioned based on the
Rate DP parameter.

Range: No limits

Parameter 22

Alarm Delay

The number of seconds you want the instrument to delay before either a HI shutoff or LO
shutoff alarm after detecting a flow rate that is out of tolerance. This avoids nuisance
shutdowns and gives the system time to clear a problem.

If a product is easily liquefied, set a very short delay to prevent large spills. If a product
tends to plug or bridge set a longer delay.

Range: 0 decimal places. Must be > or = 0.

Parameter 23

Rate Setpoint

The Rate Setpoint is the ingredient target flow rate (Loss in Weight) you want to
maintain for your process. The decimal point is positioned based on the Rate DP
parameter.

Range: Must be > or = 0, < the maximum rate set for rate calibration.

Parameter 24

REC_P_Limit

The proportional term of the PI loop is truncated to this value. Setting this parameter to a
low value makes the system more immune to glitch disturbances, such as someone
nudging the scale, at the expense of making reaction to actual changes slower.

Range: > 0, < 100.0, 1 decimal place.