Hardy HI 1769-FC User Manual

Page 48

Advertising
background image


43

Chapter 4

Word

Offset

Description

RATESETPOINT

11

Total . (MSW)

STATE

12

State

VERSION

13

Firmware version

STATUS

14

Statusword (See Statusword below)

COUNTER

15

Statusword

At word 14, the module returns a binary statusword where each bit indicates a state or
condition within the module. To interpret these states, note which bits are ON and use the
chart below to match each bit location to the state it represents.

For Example: If the statusword is 69 (45 hex) with a binary value of 0000 0000 0100
0101, bits 0, 2, and 6 are on. Bit 0 indicates an A/D conversion error, bit 2 indicates
status is ON and bit 6 indicates a shutdown error.

STATUSWORD bit positions refer to these variables:

Word

#

Definition

ERRORADCONVERT 0x0001/0

Millivolt return from the load cell
system is out of range for the unit.

ERRORADFAILURE

0x0002/1

Unit’s A/D converter not responding.

STATUS_ON

0x0004/2

System on or off

ERRORLOWALARM 0x0008/3

Low

alarm

ERRORHIGHALARM 0x0010/4

High

alarm

ERRORCONTROL_LOST

0x0020/5

Controller communication failure

ERROR_SHUTDOWN 0x0040/6

Shutdown

ERROR_RANGE

0x0080/7

Out of range value

ERROR_REC

0x0100/8

REC value over high limit

ERROR_RECMINUS

0x0200/9

REC value below low limit

ERROR_REFILL_OVER

0x0400/10

Exceed refill limit

STATUS_REFILL 0x0800/11

Refill

process

active

STATUS_BATCH_COMPLETE 0x1000/12

Batch

process

completed

ERROREEPROMWRITE 0x4000/14 EEPROM

Hardware

Error

STATUSCHANENABLED

0x8000/15

Set if channel is enabled

States (Word 12 of input table)

Mode (state) Table

Mode

Value

IDLE_MODE 0
AUTO_MODE 1
MANUAL_MODE 2
START_MODE 3
STOP_MODE 4
SHUT_OFFMODE 5
PAUSE_MODE

6