HI 1769-WS/HI 1769-2WS WEIGH SCALE MODULE

4-2

FIG. 4-2 MODULE LEDS HI 1769-2WS DUAL

CHANNEL

LEDS

The module has a Scale LED and an OK LED associ-
ated with it. The LEDs may be green, red or off. They
may be steady, Fast Flashing (5 Hertz) of Slow Flash-
ing (1 Hertz)

Scale Data
LEDs

Steady Green

Running (Normal)

Slow Flashing Green Error No Calibration
Steady Red

Error ERRORADFAILURE -
(hardware induced) status bit is
set.

Flashing Red

Read AD Convert Error.

LED is Off

Channel is not Enabled

OK Module
Status LED

Fast Flashing Green

Module communicating with
PLC. (Normal)

Slow Flashing Red

Module is not Communicating
with the PLC (Not Normal)
Error, configuration/error in
PLC addressing

NOTE:

Slow Flashing Red appears briefly when powering up.

NOTE:

*Contact Hardy Customer Support for assistance.