Hardy HI 1769-2WS User Manual

Page 54

Advertising
background image

HI 1769-WS/HI 1769-2WS WEIGH SCALE MODULE

4-20

READPARAM0
0x69
Read a parameter block.
Weight values are
formatted according to the
Metric parameter.

O:0 = 0x69
O:1-O:15 = unused

I:0 = 0x69
I:1 = 0
I:2 = ChanActive
I:3 = Metric
I:4 = WAVERSAVER
I:5 = NumAverages
I:6 = ZeroTrackEnable
I:7 = ROCtimebase
I:8 = AutoZeroTolerance,
LSW
I:9 = AutoZeroTolerance,
MSW
I:10 = MotionTolerance, LSW
I:11 = MotionTolerance, MSW
I:12 = ZeroTolerance, LSW
I:13 = ZeroTolerance, MSW
I:14-I:15 = unused

READPARAM1
0x6A
Read a parameter block.
This block contains some
non-user settable
calibration parameters
zerocount = A/D counts at
the last ZEROCMD
calzerocount = A/D counts
at zero weight, as obtained
at the last calibration
CalLowCount: A/D counts
at CalLowWeight
CalHighCount: A/D counts
at Span Weight (Hard
Calibration only)

O0 = 0x6A
O:1-O:15 = unused

I:0 = 0x6A
I:1 = 0
I:2 = tareweight LSW
I:3 = tareweight MSW
I:4 = SpanWeight LSW
I:5 = SpanWeight MSW
I:6 = CalLowWeight, LSW
I:7 = CalLowWeight, MSW
I:8 = zerocount, LSW
I:9 = zerocount, MSW
I:10 = calzerocount, LSW
I:11 = calzerocount, MSW
I:12 = calLowCount, LSW
I:13 = calLowCount, MSW
I:14 = calHighCount, LSW
I:15 = calHighCount, MSW

Command

Required Output Table Values
Written by User (PLC)

Input Table Response
From Weigh Scale

Advertising