HI 1769-WS/HI 1769-2WS WEIGH SCALE MODULE

4-10

Step 8.

Click in the Description Text Box. Type in
a description of the module.

Step 9.

Click on the down arrow to the right of
Comm Format to open the pull down list.

Step 10.

Click on Data-INT to select the Comm
Format.

Step 11.

Use the up or down arrows to the right of
Slot, to select the slot number for the
installed HI 1769-WS or HI 1769-2WS.

Step 12.

Under Connection Parameters/Input use
the up or down arrows to select 32 words.

Step 13.

Under Connection Parameters/Output use
the up or down arrows to select 32 words.

Step 14.

Under Connection Parameters/Configura-
tion use the up or down arrows to select:

For Firmware REV A - 0 words.

For other Firmware REVs - 48 words.

Step 15.

Click on the “Finish” button.

Parameters for the

HI 1769-WS Module

About Parameters

The data types that can appear in the I/O files are:

16 bit integer

32 bit integer

32 bit IEEE float.

NOTE:

In the 32 bit types, the least significant word comes
first, followed by the most significant word.

Weight values are displayed as either 32 bit integers,
or as 32 bit float depending on the value of the “Met-
ric” parameter. (See Parameter Table 4-1 below)
Each channel has a CHANNEL STATUS WORD,
with bits set to indicate the state of that channel. The
bit values are: