Chapter 4 - Setup

4-13

The configuration data is sent from the PLC to the HI
1769-WS module at power-up. The module uses these
parameters provided that:

1.

The parameters are in the correct range. Ille-
gal values will be rejected.

2.

The “CopyConfig” word (0 for channel 0, 24
for channel 1) is set to 1.

INT parameters are 2 byte integers

DINT parameters are 4 byte integers

REAL parameters are 4 byte IEEE
floating point numbers

NOTE:

Parameters labeled “REAL or DINT” will be inter-
preted as floating point or integer according to the
value of the “METRIC” parameter of the channel. If
bit 6 (0x40) of METRIC is set the parameter is float-
ing point. If bit 6 is not set, it is a fixed point integer,
with 0-7 decimal places as determined the first 3 bits
of the METRIC parameter.

Parameter

Offset (In

Words)

Data Type

Ch0CopyConfig

0

INT

Ch0ChanActive

1

INT

Ch0Metric

2

INT

Ch0Waversaver

3

INT

Ch0NumAverages

4

INT

Ch0ZeroTrackEnable

5

INT

Ch0AutoZeroTolerance

6

REAL or INT

Ch0MotionTolerance

8

REAL or INT

Ch0ZeroTolerance

10

REAL or INT

Ch0SpanWeight

12

REAL or INT