Hardy HI 1769-2WS User Manual

Page 52

Advertising
background image

HI 1769-WS/HI 1769-2WS WEIGH SCALE MODULE

4-18

WRITEMETRIC
3
Writes the Metric
Parameter. Does NOT save
the value of the metric
parameter to non-volatile
memory.

O:0 = 3
O:1 - unused
O:2 - unused
O:3 - New METRIC value

I:0 = 3
I:1 = COMMAND STATUS
I:2-I:15 See NOCMD,
continuously updating

WRITENONVOLATILE
4
This command is normally
not needed, since the
commands that write
parameters automatically
save values to non-volatile
memory. Exceptions are the
ZEROCMD, TARECMD,
and WRITEMETRIC,
which do not automatically
save.

O:0 = 4
O:1-O:15 (unused)

I:0 = 4
I:1 = 0
I:2-I:15 See NOCMD,
continuously updating

RELOADNONVOLATILE
0X10
Reread the non-volatile
memory

O:0 = 0x10
O:1-O:15 (unused)

I:0 = 0x10
I:1 = 0
I:2-I:15 See NOCMD
continuously updating

CALLOWCMD
0x64
Do the low step of a Hard
Calibration.
Results saved to non-
volatile memory.

O:0 = 0x64
O:1-O:15 (unused)

I:0 = 0x64
I:1 = COMMAND STATUS
I:2-I:15 See NOCMD,
continuously updating

CALHIGHCMD
0x65
Do the high setpoint of a
Hard Calibration.
Results saved to non-
volatile memory.

O:0 = 0x65
O:1-O:15 (unused)

I:0 = 0x65
I:1 = COMMAND STATUS
I:2-I:15 See NOCMD,
continuously updating

C2CALCMD
0x66
Do a C2 Calibration.
Results saved to non-
volatile memory

O:0 = 0x66
O:1-O:15 (unused)

I:0 = 0x66
I:1 = COMMAND STATUS
I:2-I:15 See NOCMD,
continuously updating

Command

Required Output Table Values
Written by User (PLC)

Input Table Response
From Weigh Scale

Advertising
This manual is related to the following products: