Chapter 4 - Setup

4-7

On some PLC platforms it may be necessary to enter
the Vendor ID, the Product Type, the Product Code,
Input/Output Words and Extra Data Length. See
below:

HARDY_VENDOR_ID 0x102 (258 decimal)

HARDY_PRODUCT_TYPE 0x54 (100 decimal)

HARDY_PRODUCT-CODE 5

Input Words - 32

Output Words - 32

Extra Data Length - 0 for Firmware REV A or 48

for later Firmware REVs.

Step 6.

Click on the “Apply.” button.

Step 7.

“OTHER” appears under the Part # col-
umn heading. (See Fig. 4-8)

FIG. 4-8 I/O CONFIGURATION DIALOG BOX

Step 8.

The HI 1769-WS I/O is configured and
ready to communicate with the
MicroLogix 1500 Processor.

Configuring the

HI 1769-WS in
RSLogix 5000 for
CompactLogix

To set up communication between the CompactLogix
Processor and the Weigh Scale Module you will need
to do the following in RSLogix 5000:

Step 1.

Click on the + next to I/O Configuration.
(See Fig. 4-9).