Cal low command (callowcmd), Cal high command (calhighcmd), C2 cal command (c2calcmd) – Hardy HI 1756-2WS User Manual

Page 42

Advertising
background image

HI 1756-WS WEIGH SCALE MODULE

4-14

Channel Number: 0 or 1
Number of Elements: 8

Error Return Values: None

Cal Low Command
(CALLOWCMD)

The Cal Low Command sets the “calLowCount”
parameter to the current A/D average counts when
doing a hard calibration. An Integrated Technician
function gets called during low calibration.

Command Number: 0x64 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8

Error Return Values:

STATUSWORD - there was a conversion error,
weight in motion or an A/D error or all three.

HARDCALFAILCOUNTS - less than 100
counts between the zero and the span weights.

Cal High
Command
(CALHIGHCMD)

The Cal High Command - Sets the Span Weight
parameter to the current A/D average counts when
doing Hard CAL.

Command Number: 0x65 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8

Error Return Values:

STATUSWORD - there was a conversion error,
weight in motion or an A/D error or all three.

HARDCALFAILCOUNTS - there are less than
100 counts between the zero and the span
weights.

C2 Cal Command
(C2CALCMD)

The C2 Cal Command - Performs a C2 Calibration.
Uses CalLowWeight as the reference point.

Command Number: 0x66 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8

Advertising
This manual is related to the following products: