Section 4: Block Reads

15

SECTION 4 BLOCK READS

4.1.

SCOPE

Chapter 4 covers block read commands for the PROFIBUS Interface Option. Programmers
and users should be familiar with this chapter before operating the PROFIBUS Interface
Option.

4.2.

TRANSFER COMMANDS

4.2.1

OVERVIEW OF TRANSFER COMMANDS

1. PROFIBUS Interface Card maximum buffer size: 112 byte

2. Siemens PLC

TI 505 Series PLCs

Requires the Field Interface Module (FIM) to communicate over PROFIBUS.

Can continually exchange up to 32 words or 64 bytes for both PLC input and

output with each client device.

S5 Series PLCs

Requires IM 308C Module to communicate over PROFIBUS.

Can continually exchange up to 244 bytes for PLC input and output with each

client device.

S7 Series PLC

PROFIBUS ready, does not require additional modules.

Can continually exchange up to 244 bytes for PLC input and output with each

client device.

3. Allen-Bradley PLC5 Series

Requires PROFIBUS DP module to communicate over PROFIBUS.

Can continually exchange up to 244 bytes for both PLC Input and Output with

each client device.

4.2.2

OVERVIEW OF BLOCK TRANSFER COMMANDS

1. The PLC server determines the amount of bytes that can be

transferred; not the PROFIBUS interface option.

2. When using the HI 2151 Series PROFIBUS interface, the user can

select the Block Read Data Summaries and Block Write Commands as
required. However, the amount of bytes that can be transferred is
dependent on the data transfer capability of the server being used.

3. The ladder logic program provides the server with the ability to read

and write weight data by referencing the PROFIBUS address, the byte
numbers and number of bytes.

PLC

LADDER LOGIC

PROGRAM

WRITE/READ
#5400 (hex) +
BLOCK READ
DATA NUMBER

RESPONSE
# BETWEEN
14-20 or #23 (hex) +
DATA REQUESTED

DATA EXCHANGE

BLOCK TRANSFER

Advertising