Section 7: Selectable Writes

49

Dead band Value #6

Set point #7

Set point Value #7
Preact Value #7
Dead band Value #7

Set point #8

Set point Value #8
Preact Value #8
Dead band Value #8

2
2
2

2
2
2

4
4
4

4
4
4

54
55
56

57
58
59

36
37
38

39

3A
3B

NOTE: The relays must be disabled by using Parameter #20 before performing a Force Relay with

Parameter #19.

7.7.2

SEND TARE VALUE

Send Tare Value

#

Words

#

Bytes

Parameter

#

Hex #

Send Tare Value

2

4

60

3C

7.7.3

SCALE CALIBRATION PARAMETERS

Use Block Write to do an actual calibration.

7.7.4

STICKER VALUE (THIS DATA IS NOT VALID FOR THE HI 2151/30WC)

Sticker Value

#

Words

#

Bytes

Parameter

#

Hex

#

Sticker Value

2

4

78

4E

7.7.5

CONFIGURATION OF RATE-OF-CHANGE

Configuration of Rate-of-Change

# Words

#

Bytes

Parameter

#

Hex

#

Displayed Rate-of-Change time (0 = Sec, 1 = Min, 2
= Hrs)

Rate-of-Change time base evaluation period in
seconds

Time base evaluation period:

0 = 1 second

5 = 6 seconds 10 = 60 seconds

1 = 2 sec.

6 = 10 sec.

11 = 120 sec.

2 = 3 sec.

7 = 12 sec.

12 = 240 sec.

3 = 4 sec.

8 = 15 sec.

13 = 450 sec.

4 = 5 sec.

9 =360 sec.

14 = 900 sec.
15 = 1800 sec.

1

1

2

2

80

81

50

51