KEYENCE EX-V Series User Manual

Page 70

Advertising
background image

Chapter 4 Use of Data Processing Functions

4

60

Difference between peaks (bottoms) [b-2]

Measures the difference between the maximum and minimum values of the peak
(bottom ) values during a specified period (sampling time).
The following two types of measurement are available:

1. "b-20" Difference between peak values measurement: Measures the difference

between the maximum and minimum values of the peak values.

2. "b-21" Difference between bottom values measurement: Measures the differ-

ence between the maximum and minimum values of the bottom values.

Timing diagram

For "b-20" measurement
External trigger mode

The sampling period is between the UP edge of the timing input (hold-reset
input) and the UP edge of the next timing input.

The value measured at the instant when the timing input turns ON is displayed/
output.

The EX-V series determines the peak value when the measured value
decreases from the maximum value by a specified hysteresis value. Take this
into account when inputting the timing signal.

Reference: To clear the measured value being held and start the measurement
again, short-circuit the hold-reset and GND terminals.

For "b-21" measurement
External trigger mode

The sampling period is between the UP edge of the timing input (hold-reset
input) and the UP edge of the next timing input.

The value measured at the instant when the timing input turns ON is displayed/
output.

The EX-V series determines the bottom value when the measured value
increases from the minimum value by a specified hysteresis value. Take this
into account when inputting the timing signal.

Reference: To clear the measured value being held and start the measurement
again, short-circuit the hold-reset and GND terminals.

(t)

0

ON

OFF

p1

p2

p4

p3

(p1-p2)

(p4-p3)

When the power is turned ON or the hold-reset signal is input,
the display shows " " until the first timing signal is input.

Displayed value

Timing input

Sampling period

Sampling period

(t)

0

ON

OFF

b2

b1

b3

b4

(b2-b1)

(b3-b4)

When the power is turned ON or the
hold-reset signal is input, the display
shows " " until the first timing
signal is input.

Displayed value

Timing input

Sampling period

Sampling period

Advertising