KEYENCE EX-V Series User Manual

Page 86

Advertising
background image

Chapter 4 Use of Data Processing Functions

4

76

Normal measurement function [b-0]

Displays/outputs the measured value continuously.

Timing diagram

*

When the timing input is turned ON, the display and comparator output is held.

Peak hold function [b-1]

Measures the "maximum value" during a specified period (sampling period).
For the peak hold function, the sampling period can be specified with the
combination of the trigger mode and delay time settings.

➮ For the details of the trigger mode and delay time, refer to pages 69 and 70.
➮ For the details of flicker delay, refer to pages 70 to 73.

The sampling period is between the UP edge of the timing input (hold-reset
input) and the UP edge of the next timing input.

The value measured at the instant when the timing input turns ON is displayed/
output.

Reference: To clear the measured value being held and to start the measurement
again, short-circuit the hold-reset and GND terminals.

(t)

0

ON

OFF

ON

OFF

ON

OFF

LOW OUT

GO OUT

HIGH OUT

ON

OFF

ON

OFF

Timing input

HIGH limit value

LOW limit value

Displayed value

(t)

0

ON

OFF

When the power is turned ON or the hold-reset signal is input,
the display shows " " until the first timing signal is input.

Displayed value

Timing input

Peak hold
value

Sampling period

Sampling period

Sampling period