KEYENCE EX-V Series User Manual

Page 93

Advertising
background image

Chapter 4 Use of Data Processing Functions

4

83

Internal trigger mode (Example of internal trigger up )

The sampling operation starts when the sampling delay time elapses after the
measured value exceeds the trigger level. When the sampling period elapses,
the internal timing signal is turned ON and the measured value at the instant is
displayed/output.

For the internal trigger down operation, the trigger point is the instant when
the measured value falls below the trigger level.

The instant when the sampling starts, the strobe output turns ON.

Turning the strobe output from ON to OFF results in the off-delay of 2 ms for
updating the comparator output.

Reference: To clear the measured value being held and to start the measurement
again, short-circuit the hold-reset and GND terminals.

Flicker mode

The internal timing signal is input once at each flicker time and the value at the
instant is displayed/output.

ON

OFF

ON

OFF

ON

OFF

0

(t)

When the power is turned ON or the hold-reset signal
is input, the display shows " " until the first
measured value is determined.

Displayed value

Internal data reset

Internal timing

Strobe output

Trigger
point

Average hold value

Sampling delay

Sampling period

Sampling delay

Sampling period

Trigger level

(t)

0

ON

OFF

When the power is turned ON or the hold-reset signal is input,
the display shows " " until the first measured value is
determined.

Displayed value

Internal timing

Average hold value

Sampling period Sampling period Sampling period

Flicker time