Chapter 1

Introduction

5

Power requirements

Every CyberDome II dome requires a 24 VAC power supply to operate the PTZ, camera, and heater/fan, if
present. The startup and running power requirements vary depending on the model (Table 2).

Cable management

Follow all local codes for cable management. As a general rule, you can fill a cable conduit to a maximum of
60% of its capacity. You must maintain 40% free space. A variety of factors will determine how many cables
you can run into the dome. Capacity limitations include:

number of cables

size of the cables

use of single-conductor or multiple-conductor cable

use of a junction box

Figure 4 provides an illustration of the cable capacity of three typical applications. It is important to note that
all cables of the same gauge are not of the same diameter.
Manufacturer, shielding, and rating affect the actual
diameter of cables of the same gauge. GE leaves the selection of the appropriate cable to the discretion of the
installer who is working with the local codes of the installation site.

Figure 4. Three acceptable typical cabling scenarios

Table 2.

Power requirements at 24 VAC (±4 VAC) operating voltage

Model

Startup power

Running power

Minimum power source to use

Dome with fan

25 VA

20 VA

40 VA

Dome with 12 W heater/fan (×2)

93 VA

45 VA

56 VA

Rugged and HD dome with 23 W heater/fan (×2)

153 VA

66 VA

100 VA

CAUTION: Use only a Class 2 power supply of the required output rating as listed on individual units and specified.

Percentage conduit fill = 38%, includes:

• Video: one 59U/6U coaxial (0.24 in. dia)
• Data: two 20 AWG UTP (0.19 in. dia)
• Power: one 16 AWG UTP (0.25 in. dia)

Percentage conduit fill = 53%, includes:

• Video: one 59U/6U coaxial (0.24 in.dia)
• Data: two 20 AWG UTP (0.19 in. dia)
• Power: one 16 AWG UTP (0.25 in. dia)
• Alarms: 24 AWG UTP (0.11 in. dia.)
• Relays: 24 AWG UTP (0.11 in. dia.)

3/4 in. dia.

Video

Power

Relays (two)

Data

(two, daisy-chained)

Alarms

(multiconnector)

3/4 in. dia.

Video

Power

Data

(two, daisy-chained)