Microtel Series 500 User Manual

Page 29

Advertising
background image

22


By using the cursor and Select keys, each week day may be individually programmed
with information which tells the dialer when to call or when to postpone calls. The time
period may be programmed from midnight (0000 hours) to one minute before midnight
(2359). One of four actions may be selected for each time period.

ENABLE

Enables calls for the time period entered for that day

DISABLE

Disables calls for the time period entered for that day

ALWAYS

Forces the equivalent of an ENABLE 0000-2359

NEVER

Forces the equivalent of a DISABLE 0000-2359


The Call-At times direct the system to place calls (looking for an acknowledgment) at a
specific time for each day of the week. Times should be entered in 24 hour format, and
may be reset to a No-Call value (****) by entering any number greater than 2359. Calls
will be placed regardless of the alarm condition of the monitored channels, and will be
placed to the telephone numbers contained in the list specified by the System Level’s
Call At List value.

After selecting the Call Periods and Call At values for each day, exit the Calendar
Screen by moving to and selecting EXIT.

IV.C.11.

Power Failure Channel


A sub-function under the System Setup Screen, the Power Failure Setup Screen allows
the programming of all parameters associated with the internal Power Failure Alarm.
The information below details the purpose and the programming of each of these
channel related functions. To program the Power Failure Channel data choose
POWER while in the SYSTEM SETUP screen.