I n s t a l l i n g a n A f t e r c o o l e r

( O p t i o n a l )

You can add an aftercooler to the D Carousel Dryer by ordering the optional after-
cooler assembly. Installation is easy.

The optional aftercooler requires a source of city, tower, or chiller water and a dis-
charge or return line. You can use water at temperatures up to 85°F (30°C). But the
water flow should be at least 1 gal/min (3.8 liters/min) for models D15, D25, D50;
or 2 gal/min (7.6 liters/min) for models D75 and D100.

1

Stop the dryer and lockout the main power.

2

Remove the cover plate from the right side of the aftercooler housing on the
dryer by removing the five screws.

3

Inspect the condition of the gasket. If the gasket is damaged, replace the
gasket.

4

Insert the aftercooler assembly into the aftercooler housing. Make sure the
staggered holes in the aftercooler mounting plate align with the holes in the
aftercooler housing.

(continued)

C - 1

l A p p e n d i x

TIP: Make the water supply and dis

charge / return connections with

flexible hoses at least 24 in. (61 cm)

long. This allows you to easily

remove the aftercooler assembly for

cleaning.

TIP: If an optional flow control is also

being installed with the aftercooler,

the manual shut off valve should be

installed on the inlet line for the flow

control.