121

VM-3240VA/3360VA rear

CTRL IN 1

COM 1

CTRL IN 2

COM 3

CTRL IN 3

COM 2

CTRL IN 4

COM 4

NC
CTRL IN 5

COM 5

Not used

Not used

Not used

Not used

CTRL IN 6

COM 6

NC

Emergency control
input terminals 1 – 4

Emergency control
input terminals 5 and 6

Contact
control

Voltage
control

Shield

Orange/White

Orange

Green/White

Blue

Blue/White

Green

Brown/White

Brown

Green/White

Green

Orange/White

Blue

Blue/White

Orange

Brown/White

Brown

Connector name

Pair

Assignment

RJ45 connector

pin No.

Cable color

(T568B type)

Cable color

(T568A type)

Shield

Orange/White

Orange

Green/White

Blue

Blue/White

Green

Brown/White

Brown

CTRL IN 1 – 4

CTRL IN 5 – 6

Green/White

Green

Orange/White

Blue

Blue/White

Orange

Brown/White

Brown

RJ45 connector
Pin No.

1
2

5

4

3

6
7
8

RJ45 connector
Pin No.

1
2

5

4

3

6
7
8

CTRL IN 1

Fire Alarm

COM 1

1

2

3

4

CTRL IN 2

COM 2

CTRL IN 3

COM 3

CTRL IN 4

COM 4

CTRL IN 5

COM 5

24 V

CTRL IN 6

COM 6

Emergency Reset
switch

[Terminal assignment to the emergency control inputs]

14.5.1. External emergency control equipment connection

An emergency broadcast (Evacuation EV or Alert EV) can be activated by external controls such as an
automatic fire alarm activation signal.
To reset the emergency status, press the Emergency Reset switch.

Note
Contact inputs 1 – 5 are no-voltage
make contact inputs. Input 6 is an
isolated voltage input which
activates when the polarity of the
applied voltage (24 V DC is kept
applied to this terminal under
normal condition) is reversed.

Advertising