Unit id number settings, Compression settings, Refer to – Toa VM-3000 Series User Manual

Page 90

Advertising
background image

90

[RM-300MF]

Unit ID No.

Switch No. 5

1

ON

2

OFF

[RM-200M]

Unit ID No.

Switch No. 1

Switch No. 2

1

ON

ON

2

OFF

ON

3

ON

OFF

4

OFF

OFF

12.3. Compression Settings

(RM-300MF: Switch 6 operation or RM-200M: Switch 6 operation)

To perform compression settings, use the DIP switch No. 6 for both the RM-300MF and RM-200M.

Note
DIP switch is located on the bottom surface for the RM-300MF and on the side surface for the RM-200M.

Setting the DIP switch to ON enables announcements to be broadcast without distortion even if excessive
input signal is applied to the microphone. (Default: ON)

Note
Be sure to press the VM reset switch located on the VM-3240VA's and VM-3360VA's front panel to cycle the
system power when the unit ID has been changed with the system power switch turned on.

12.2. Unit ID Number Settings

(RM-300MF: Switch 5 operation or RM-200M: Switch 1 and 2 operation)

To set the unit ID number, use the DIP switch 5 for the RM-300MF and DIP switches 1 and 2 for the RM-
200M.

Note
The DIP switch is located on the bottom surface for the RM-300MF and on the side surface for the RM-200M.

Set the unit ID numbers of the RM-300MF and RM-200M.
Make the Setting Software-assigned ID numbers for these units and the ID numbers set by their DIP switches
identical. (All DIP switches set to ON by default)

(For setting instructions using the Setting Software, refer to the separate Setting Software Instructions, "RM
function key settings.")