Equipment operation upon failure detection – Toa VM-3000 Series User Manual

Page 51

Advertising
background image

51

Failure indicator

LCD

Buzzer

GENERAL

FAULT

F A U L T

V A

A M P L I F I E R

>

Communications Failure indicator

COM

FAULT

A failure has occurred in communications between the unit and the VM-3360VA or VM-3240VA.
The previous status is automatically restored if communications return to normal.

10.4.1. Equipment operation upon failure detection

[VM-3240VA and VM-3360VA]

The buzzer sounds, the failure indicator flashes yellow and failure information is displayed on the LCD screen.

Equipment operation upon failure detection

In this event, a failure of the contents shown on the LCD screen has occurred within the system. Pressing the
amplifier’s [OK] key to acknowledge the failure or acknowledging the failure by way of the Fireman’s
Microphone stops the buzzer and switches the yellow failure indicator from flashing to steady-on mode. (Refer
to "Failure Acknowledgement" on

page 54

).

If the failure is reset at the amplifier, the failure indicator goes out. However, if the cause of the failure has not
been remedied, the unit will return to failure status. (Refer to "Failure Reset Operation" on

page 55

).

[VM-3240E and VM-3360E]

The Communications Failure indicator flashes yellow.

Equipment operation upon failure detection

Advertising