IMPORTANT: Even though a minimum of only 12-inches is required, 18-inches or more is

suggested. The additional clearance is advantageous for ease of installation
and service.

IMPORTANT: When fire sprinkler systems are located above the dryers, a minimum of

18-inches above the dryer console (module) is required. Dryers may be

positioned side wall to side wall however, a 1/16" minimum allowance is
required between dryers (or wall) for ease of installation and maintenance.
Allowances must be made for the opening and closings of the control door

and the lint door.

D. FRESH AIR SUPPLY

When the dryer is operating, it draws in room air, heats it, passes this air through the basket (tumbler), and
exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If
the make-up air is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems
and sail switch "fluttering" problems may result, as well as premature motor failure from overheating.

Air supply (make-up air) must be given careful consideration to assure proper performance of each dryer. An
unrestricted source of air is necessary for each dryer. An air flow of 1,200 cfm (cubic feet per minute) must be

supplied to each gas and electric dryer and 1,350 cfm (cubic feet per minute) must be supplied to each steam

dryer. As a general rule, an unrestricted air entrance from the outdoors (atmosphere) of a minimum of 1-1/2

square feet is required for each dryer.