c. Flexible hoses or couplings must be used. The dryer vibrates slightly when it runs and this will cause

the steam coil connections to crack if they are hard piped to the supply and return mains.

d. Shut-off valves for each dryer should be installed in the supply line, return line, and drip trap return line.

This will allow the dryer to be isolated from the supply main and the return main if the dryer needs
maintenance work.

e. Install an inverted bucket steam trap and check valve at least 12-inches below the steam coil as close to

the coil as possible.

1) A trap with capacity of 1,200 pounds of condensate per hour at 125 psi is needed for each unit.

f. The supply line and the return line should be insulated. This will save energy and provide for the safety

of the operator and maintenance personnel.

g. Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly

causing steam coil damage. ALL horizontal runs of steam supply piping should be pitched 1/4-inch for
every one (1) foot back towards the steam supply header causing the condensate in the line to drain to the
header. Install a bypass trap in any low point to eliminate wet steam.

STEAM DAMPER SYSTEM

31