MULTIPLE DRYER VENTING (ADG-78/ADE-78) WITH 8" DIAMETER

(1200 CFM) EXHAUST CONNECTIONS AT COMMON DUCT

NO OF DRYERS

4

3

2

1

MINIMUM CROSS
SECTION AREA (SO.IN.)

315

254

200

113

MINIMUM ROUND
DUCT DIAMETER (IN.)

20

18

16

12

VERTICAL

TUMBLER

EXHAUST

MUST

ENTER

MAIN

EXHAUST DUCT AT A ¿5° ANGLE.

38 1/4 MIN

2 X D CLEARANCE

IMPORTANT. NO MORE THAN 4 DRYERS CAN

BE CONNECTED TO ONE COMMON DUCT i VENT ).

2X0 CLEARANCE

ROOF

10-INCH MINIMUM

FORMULAS TO CALCULATE DUCTING CROSS SECTIONAL AREA

CROSS SECTIONAL AREA OF A ROUND DUCT - 785

x

WHERE D - DIAMETER OF THE DUCT.

CROSS SECTIONAL AREA OF A RECTANGULAR DUCT - W x H WHERE W

WIDTH AND H

=

HEIGHT.

1

I

hF

NOTE A: OPENING MUST BE TWO (2) INCHES LARGER THAN DUCT (ALL THE WAY AROUND). THE DUCT

MUST BE CENTERED WITHIN THIS OPENING.

MULTIPLE DRYER VENTING (AD5-78)

WITH 10" DIAMETER (1350 CFM) EXHAUST CONNECTIONS AT COMMON DUCT

NOTE A

NO OF DRYFRS

4

3

2

1

MINIMUM CROSS
SFCTION AREA (50.IN.)

330

315

200

113

MINIMUM ROUND
DUCT DIAMETER (IN.)

22

20

16

12

VERTICAL DUCTING

2 X D CLEARANCE

38 1/4" MIN.

ROOF

10-INCH MINIMUM

2 X D CLEARANCE

TUMBLER EXHAUST MUST ENTER MAIN

EXHAUST DUCT AT A 45° ANGLE.

IMPORTANT: NO MORE THAN 4 DRYERS CAN

BE CONNECTED TO ONE COMMON DUCT ( VENT )

FORMULAS TO CALCULATE DUCTING CROSS SECTIONAL AREA

CROSS SECTIONAL AREA OF A ROUND DUCT = .785 x

d

' WHERE D

-

DIAMETER OF THE DUCT.

CROSS SECTIONAL AREA OF A RECTANGULAR DUCT

« IV x H

WHERE W = WIDTH AND H = HEIGHT.

—I

IV

i^TT

NOTE A: OPENING MUST BE TWO (2) INCHES LARGER THAN DUCT (ALL THE WAY AROUND). THE DUCT

MUST BE CENTERED WITHIN THIS OPENING.