IMPORTANT: Minimum duct work diameter for horizontal venting is 10-inches and for vertical

venting the minimum is 12-inches.

NOTE: Where the exhaust duct work passes through a wall, ceiling, or roof made of combustible

materials, the opening must be 2-inches larger (all the way around) than the duct. The

________ duct must be centered within this opening.

a. Outside Duct Work Protection

1) To protect thé outside end of horizontal duct work from the weather, a 90° elbow bent downward

should be installed where the exhaust exits the building. If the duct work travels vertically up
through the roof, it should be protected from the weather by using a 180° turn to point the opening
downward. In either case, allow at least twice the diameter of the duct between the duct opening euid
the nearest obstruction.

I IMPORTANT: DO NOT use screens or caps on the outside of opening of exhaust duct work. ^

VERTICAL DUCTING

HORIZONTAL DUCTING

. OPENING MUST BE TWO (2) INCHES LARGER THAN DUCT

(ALL THE WAY AROUND). THE DUCT MUST BE CENTERED
WITHIN THIS OPENING

2. Single Dryer Venting

Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct should
be laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns

as possible. It is suggested that the use of 90° turns in the ducting be avoided; use 30° and/or 45° angles
instead. The shape of the exhaust duct work is not critical so long as the minimum cross section area is
provided.

IMPORTANT: Minimum duct size for a dryer that is vented horizontally is 10-inches for a

round duct or an equivalent of 80 square inches. THE DUCT SIZE MUST

NOT BE REDUCED ANYWHERE DOWN STREAM OF THE DRYER.

IMPORTANT:

Exhaust back pressure measured by a manometer at each basket (tumbler)
exhaust duct area should not exceed 0.3 inches of water colunm.

16