18 read host watchdog timer & safety value – ADLINK ND-6054 User Manual
Page 101
Command Set
• 93
3.18 Read Host Watchdog Timer & Safety Value
( 6050, 6052, 6053, 6054,
6056, 6058, 6060, 6063 )
@Description
Read host watchdog timer setting and the safety value.
@Syntax
~(Addr)3<CR>
~
Command leading code.
(Addr) Address
ID
3
Read host watchdog setting and module safety
state value.
@Response
!(Addr)(Flag)(TimeOut)(SafeValue)<CR>
!(Addr)(Flag)(TimeOut)(SafeH)(SafeL)<CR> (6056 only)
!(Addr)(Flag)(TimeOut)(SafeA)(SafeB)(SafeC)<CR> (6058only)
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID, range (00 - FF).
(Flag)
0 : Host watchdog timer is disable
1 : Host watchdog timer is enable(1-character)
(TimeOut)
Host timeout value.
Range 01 - FF. (2-character)
One unit is 100 ms
01 = 1 * 100 = 100 ms
FF = 255 * 100 = 25.5 sec
(SafeValue)
8 channels safety state digital output value when
host is failure. (2-character)