4 read configuration – ADLINK ND-6054 User Manual

Page 72

Advertising
background image

64

Command Set

3.4 Read Configuration

( 6050, 6052, 6053, 6054,

6056, 6058, 6060, 6063 )

@Description

Read the configuration of module on a specified address ID.

@Syntax

$(Addr)2<CR>

$

Command leading code

(Addr) Address

ID.

2

Command code for reading configuration

@Response

!(Addr)(TypeCode)(BaudRate)(CheckSumFalg)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

(TypeCode)

It always be 40 (Hex) for digital I/O modules.

(BaudRate)

Current setting of communication baud rate,
refer to Table 3-1 for details.

(CheckSumFlag)

Current setting of check-sum flag, refer to Table
3-3. for details.

Advertising