15 read leading code setting – ADLINK ND-6054 User Manual

Page 94

Advertising
background image

86

Command Set

3.15 Read Leading Code Setting

( 6050, 6052, 6053, 6054,

6056, 6058, 6060, 6063 )

@Description

Read command leading code setting and host watchdog status.

@Syntax

~(Addr)0<CR>

~

Command leading code.

(Addr) Address

ID

0

Read command leading code setting.

@Response

!(Addr)(Status)(C1)(C2)(C3)(C4)(C5)(C6)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID

(Status)

(2-character)
Bit 0 : Reserved
Bit 1 : Power failure or watchdog failure
Bit 2 : Host watchdog is enable
Bit 3 : Host failure

(C1)

Leading code 1, for read configuration status,
firmware version, etc. default is $.
(1-character)

(C2)

Leading code 2, for read synchronize sampling,
digital output ,default is #. (1-character)

(C3)

Leading code 3, for change configuration.
default is %. (1-character)

(C4)

Leading code 4, for read alarm status, enable
alarm, etc. default is @. (1-character)

(C5)

Leading code 5, for read command leading code,
change command leading code, etc. default is ~.
(1-character)

(C6)

Leading code 6, this leading code is reserved.
Default is *. (1-character)