Introduction

1.6 Overview of NuDAM-6056

1.6.1 What is NuDAM-6056 ?

NuDAM-6056 provides 15 isolated digital output channels. All of the output
channels are common ground type and one of them is use the same pin with
default (use jumper to choose). The isolation voltage is up to 5000 Vrms. It
is suitable to use NuDAM-6056 in industrial environment with the dangerous
of high voltage electric shock.

1.6.2 Features of NuDAM-6056

♦ 15 bits digital open collector output with isolation protection and

common ground

5000 Vrms isolation voltage

Programmable host watchdog timer for host failure protection

Internal watchdog timer for device failure protection

Easy programming by software

Easy installation and wiring

1.6.3 Specifications of NuDAM-6056

Interface

• Interface : RS-485, 2 wires

• Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K, 115.2K

(115.2K only for firmware reversion above A4.00)

Digital Output

• Channel numbers : 15 isolation common ground output channels(the

fifteenth channel is the same with default pin,but could use jumper to
choose).

• Output

characteristic:open collector transistor

• Maximum current sink:50mA(300mA for Hardware Reversion.A2)

• Max.power dissiation:200mW(3W for Hardware Reversion.A2)

• Isolation

Voltage:5000Vrms