13 read synchronized data – ADLINK ND-6054 User Manual
Page 86
![background image](/manuals/733493/86/background.png)
78
• Command Set
3.13 Read Synchronized Data
( 6050, 6052, 6053,6054, 6058, 6060 )
@Description
After a synchronized sampling command #** was issued, you can read the
input value that was stored in the addressed module’s register and use same
method to process other module‘s data one by one.
@Syntax
$(Addr)4<CR>
$
Command leading code.
(Addr) Address
ID.
4
Read synchronized data.
@Response
ND-6050 module response :
!(Status)(DataOut)(DataIn)00<CR>
ND-6052 module response :
!(Status)(DataIn)0000<CR>
ND-6053 module response :
!(Status)(DataInH)(DataInL)00<CR>
ND-6054 module response :
!(Status)(DataInH)(DataInL)00<CR>
ND-6058 module response :
!(Status)(IOFlag)(DIn)(DataInA)(DataInB)(DataInC)<CR>
ND-6060 module response :
!(Status)(DataOut)(DataIn)00<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.