3.10 Digital Output (Continued)
( 6056, 6058 )
@Description
Set digital output port channel value at specified address. This command is
only available to modules involving the multiport digital output function.
@Syntax
#(Addr)(Port)(OutData)<CR> (6056, 6058 only)
#
Command leading code. (1-character)
(Addr)
Address ID (2-character)
(Port)
Set value to indivisual port
0H: for 6056 channel 14 to 8
0L: for 6056 channel 7 to 0
0A: for 6058 port A
0B: for 6058 port B
0C: for 6058 port C (2-character)
(OutData)
Each bit is mapping to each channel number
(2-character)
* if the port of ND-6058 is in input mode, output data to this port will be
ignore.
@Response
<CR>
or
?(Addr)<CR>
>
Command is valid.
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
#30H03<CR> (for ND-6056)
Response:
<CR>
30 Address
ID
0H
Set output to high byte
03
03 (00000011), Channel 8 and 9 are set ON other
channels are set to OFF