10 digital output (continued) – ADLINK ND-6054 User Manual

Page 81

Advertising
background image

Command Set

73

3.10 Digital Output (Continued)

( 6056, 6058 )

@Description

Set digital output port channel value at specified address. This command is
only available to modules involving the multiport digital output function.

@Syntax

#(Addr)(Port)(OutData)<CR> (6056, 6058 only)

#

Command leading code. (1-character)

(Addr)

Address ID (2-character)

(Port)

Set value to indivisual port
0H: for 6056 channel 14 to 8
0L: for 6056 channel 7 to 0
0A: for 6058 port A
0B: for 6058 port B
0C: for 6058 port C (2-character)

(OutData)

Each bit is mapping to each channel number
(2-character)

* if the port of ND-6058 is in input mode, output data to this port will be
ignore.

@Response

<CR>

or

?(Addr)<CR>

>

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

@Example

User command:

#30H03<CR> (for ND-6056)

Response:

<CR>

30 Address

ID

0H

Set output to high byte

03

03 (00000011), Channel 8 and 9 are set ON other
channels are set to OFF

Advertising