Command Set

91

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID

@Example

Example for NuDAM-6050 :

User command:

~0621121C<CR>

Response:

!06<CR>

06 Address

ID

2

Set host watchdog timer and safe state value.

1

Enable host watchdog timer.

12

Timeout value. 0x12 = 18
18 * 100 = 1800 ms

1C

1C (00011100) Digital output channel DO2, DO3
and DO4 are high, the others are low.

Example for NuDAM-6056 :

User command:

~0621121C1C<CR>

Response:

!06<CR>

06 Address

ID

2

Set host watchdog timer and safe state value.

1

Enable host watchdog timer.

12

Timeout value. 0x12 = 18
18 * 53.3 = 959 ms
18 * 100 = 1800 ms

1C1C

1C1C (0001110000011100) Digital output
channel DO2, DO3, DO4, DO10, DO11, DO12
are high, the others are low.

Advertising