7 - NEAR BOILER PIPING

7.3 Safety Relief Valve / Temperature Pressure Gauge

WARNING

Burn and scald hazard. Safety relief valve could

discharge steam or hot water during operation.

Install discharge piping per these instructions.

!

Installation of (supplied) safety relief valve shall conform to

ANSI/ASME Boiler and Pressure Vessel Code, Section IV.

• Install furnished safety relief valve using 3/4” pipe

fittings provided with boiler. See Figure 2.

• Install safety relief valve with spindle in vertical

position.

• Do not install shutoff valve between boiler and safety

relief valve.

• Install discharge piping from safety relief valve. See

Figure 2.

• Use ¾” or larger pipe.

• Use pipe suitable for temperatures of 375°F (191°C) or

greater.

• Individual boiler discharge piping shall be independent

of other discharge piping.

• Size and arrange discharge piping to avoid reducing

safety relief valve relieving capacity below minimum

relief valve capacity stated on rating plate.

• Run pipe as short and straight as possible to location

protecting user from scalding.

• Install union, if used, close to safety relief valve outlet.

• Install elbow(s), if used, close to safety relief valve

outlet and downstream of union (if used).

• Terminate pipe with plain end (not threaded).

7.4 Expansion Tank & Make-up Water

• Determine required system fill pressure, system design

temperature, and system water content.

• Boiler contains 2.6 gallons (US). Size expansion tank

accordingly.

• Consult expansion tank manufacturer for proper sizing

information. Connect properly sized expansion tank

(not furnished) as shown in

Figure 3 for diaphragm

type expansion tank.

• Adjust tank air pressure on diaphragm type expansion

tanks to match system fill pressure.

• Install air vent (furnished) as shown for diaphragm

type expansion tank system only.

• Install make-up water connections as show.

• If pressure reducing valve is used, adjust to match

system fill pressure.

• Verify clean water supply is available when connecting

cold make-up water supply to boiler.

• Use sand strainer at pump if water supply is from well

or pump.

GATE VALVE

REDUCED PRESSURE
BACKFLOW PREVENTER

FEED
WATER

PRESSURE
REDUCING VALVE

AIR SCOOP

DIAPHRAGM TYPE
EXPANSION TANK

SUPPLY PIPING

Check local codes

for maximum

distance from

floor.

FLOOR

Safety Relief Valve

Figure 2 - Safety Relief Valve Discharge Piping

Figure 3 - Diaphragm Type Expansion Tank Piping